Chilled and frozen are different jobs
A chilled cold room is designed to hold product just above freezing. A freezer room is designed to hold it well below. They use different evaporator designs, different defrost strategies and different controls, and a chilled room cannot simply be turned down to become a freezer.
As a working guide, chilled rooms are generally set between 1 and 4 degrees Celsius and freezer rooms at minus 18 or colder. Your actual target should follow your product and your food safety requirements, and some products need tighter limits than others.
Air temperature is not product temperature
A room can read 3 degrees on the wall display while a pallet of warm stock in the middle is still at 9 degrees. Air temperature responds quickly; product temperature responds slowly, especially in a densely packed room.
Probe the product, not just the air, particularly when stock has just come in. Place the sensor where it measures the room rather than the draught from the evaporator, and keep it away from the door.
Why rooms drift
When a cold room will not hold temperature, the cause is usually one of these:
- The door is open more than anyone realises, or a strip curtain is missing or damaged
- The evaporator is iced up because the defrost cycle is failing, so airflow drops away
- The drain is blocked and melt water refreezes on the floor or in the evaporator
- The condenser is blocked with dust, so the plant cannot reject heat
- The condensing unit sits in a hot, poorly ventilated courtyard or plant room
- The room is overloaded, or warm product is being loaded faster than the plant can pull it down
- A panel joint or door seal has failed, letting warm moist air straight in
Defrost is the usual suspect
Every freezer room and most chilled rooms run a defrost cycle to clear ice from the evaporator. When a heater, sensor or timer fails, the ice stays, airflow collapses and the room drifts even though the compressor is running normally.
That is why a room that runs constantly without getting cold often needs a defrost repair rather than more refrigerant. Checking the ice pattern on the evaporator tells you which it is.
Monitoring and records
A temperature display on the wall is useful, but it is not a record. If you need to show temperatures over time, use a logger or an alarmed controller that stores readings, and check it on a routine rather than only when something looks wrong.
An alarm that nobody hears is the same as no alarm. Route it to a phone or a person who is on site, and make sure whoever opens the kitchen knows what to do when it sounds.
A short daily routine
Most cold room failures give warning. A two-minute daily check catches a lot of them:
- Read the display and note it against yesterday
- Look at the evaporator for ice where there should be none
- Check the floor for water or ice
- Confirm the door closes and seals properly
- Listen for a fan that sounds different
- Keep warm stock out of the room until it has cooled